--- # if UPS is not directly connected, which server to poll for UPS status ups_primary: '' # interval at which apcupsd will poll the UPS for status ups_polltime_seconds: 60 # seconds from power failure is detected until we react to it with an onbattery event ups_on_battery_delay_seconds: 6 # will trigger on first of the following values that is true ups_shutdown_on_battery_percent: 5 ups_shutdown_on_remaining_minutes: 5 ups_shutdown_timeout_seconds: 0 # disabled by default, best to leave disabled unless testing # seconds before shutdown to send alert to users logged in ups_preshutdown_annoy_seconds: 300 # initial delay after power failure before warning users to get off the system ups_annoy_delay_seconds: 60